REGIMES OF DETERIORATED HEAT TRANSFER AT FORCED PLOW OF FLUIDS IN CURVILLINEAR CHANNELS

Get access (open in a dialog) DOI: 10.1615/IHTC3.1820
pages 95-101

Аннотация

Experimental data on heat transfer degradation when water, steam-water mixture or superheated steam is flowed through curved portions of pipes of different diameters and curviture radii are presented. The pressure variation is within the range of 20 to 295 bars and the enthalpy varies from 210 to 3350 Kjoule/kg.
Within a certain region of enthalpies at subcritical parameters, critical heat fluxes in bands are found to be smaller than in straight pipes, whereas at higher enthalpies the reverse is true. In all cases the boiling crisis develops near inside part of the bend.